Final | 5/10/2018 | 5/11/2018 | 5/11/2018 | A | PASS |
James Ady
|
|
|
garage code is 3535 Phone #: ###-#### Inspection requested via web by caleb Larson final ok
|
Rough-In Permanent Service | 3/9/2018 | 3/12/2018 | 3/12/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by caleb Larson Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 3/8/2018 | 3/9/2018 | 3/9/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by caleb Larson 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage by nail plates. 356.28- Flexible non metallic conduit cut ends shall be trimmed. 422.10- Furnace. Manufacturers instructions state 12 ga. branch circuit conductors minimum shall feed furnace.
|
Issue PAID IN FULL permit | | | 3/8/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/8/2018 | | DONE |
|
|
|
This permit was created on the web by caleb Larson
|