ELE-Aging Inspection | 8/3/2020 | 8/3/2020 | 8/3/2020 | | PEND |
Daryl DeGrange
|
|
|
This permit is still open with the City of Boise. please call 208 ###-#### with a progress report or any questions. If your job is complete, or schedule an final inspection online. Thank you!
|
ELE-Aging Inspection | 5/4/2020 | 5/4/2020 | 5/4/2020 | | FAIL |
Daryl DeGrange
|
|
|
Permit lacking required final inspection. Pursuant of contacting aging permit applicants is on hold until required Soical Distancing has been removed.
|
Electrical Rough-In | 4/10/2018 | 4/10/2018 | 4/10/2018 | P | PASS |
Eric Story
|
|
|
Luanne Phone #: ###-#### Basement bathroom ok to cover
|
Conference | 3/16/2018 | 3/16/2018 | 3/16/2018 | P | DONE |
Eric Story
|
|
|
Lou Ann Phone #: ###-#### Discussed feeding bath receptacle and lights from a new 20 amp branch circuit and not feeding any other circuit. As noted on failed inspection
|
Electrical Rough-In | 3/9/2018 | 3/9/2018 | 3/9/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Call when you are on your way- Lou Ann Phone #: ###-#### 210.52(D)- Bathroom receptacles shall be on a dedicated 20 amp circuit. Exception allows bath lighting to be on same circuit if circuit does not leave bathroom and all wiring would be on 20 amp branch circuit and 12 ga. wire to all. Bath receptacle fed with 12 ga but 14 ga leaves box. Conference required to discuss.
|
Application received | | | 3/9/2018 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 3/9/2018 | | DONE |
|
|
|
|