Permit Information
Permit NumberELE18-00916
StatusFinaled
Name POWERHOUSE ELECTRIC
Site Address 3411 E TRIFECTA LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: New Home
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/1/20186/4/20186/4/2018APASS
DetailsJames Ady
garage code 4124 Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made final ok
Final5/30/20185/31/20185/31/2018AFAIL
DetailsRock A. Hudson
garage code 4124 Phone #: ###-#### Inspection requested via web by Darryn Coburn
BCC 04-05-24(D)- Inspector shall have access to all boxes. Garage receptacle partially blocked unable to test.
210.8- All garage receptacle outlets shall have GFCI protection.
210.52- A receptacle outlet shall be located with in 6' of wall at top of stair on level 2.
314.17(C)- Where boxes moved for tile NM sheath shall enter box at least 1/4" minimum.
314.25- All boxes shall have a cover. Level 3 mechanical room.
352.30- Service PVC riser shall be secured with in 36" of meter.
Rough-In Permanent Service3/19/20183/19/20183/19/2018PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough in ok p/s u/g n ok
Issue PAID IN FULL permit  3/9/2018 DONE
Payment received via Govolutions
Application received  3/9/2018 DONE
This permit was created on the web by Darryn Coburn