Final | 7/30/2018 | 7/31/2018 | 7/31/2018 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Final ok
|
Rough-In Permanent Service | 3/16/2018 | 3/16/2018 | 3/16/2018 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 3/15/2018 | 3/15/2018 | 3/15/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey 110.3- SER shall be secured by listed strap. Nail strap used listed for conduit only. 210.11(C)(4)- Circuit for garage receptacles shall have no other outlets. transformer. 300.4(B)(1)- Where NM cable passes thru punched or drilled holes a bushing or listed connector shall be installed to protect from physical damage. Furnace. 314.23(B)- Power bath fan hanging on wire. Secure fan in place. 352.46- A listed bushing shall be installed on service PVC riser. * What is purpose for wire hanging from ceiling by back door?
|
Issue PAID IN FULL permit | | | 3/15/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/15/2018 | | DONE |
|
|
|
This permit was created on the web by Neal Rumsey
|