Final | 5/22/2018 | 5/23/2018 | 5/23/2018 | A | PASS |
James Ady
|
|
|
Inspector James Ady approved a time frame of 8-10 AM. Karrigan, tech: ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting Final ok
|
Final | 5/17/2018 | 5/18/2018 | 5/17/2018 | A | CANC |
James Ady
|
|
|
Homeowner phone: ###-#### Phone #: ###-#### >> Inspection requested via web by BRS Permitting Inspection cancelled from web by: BRS Permitting
|
Final | 5/2/2018 | 5/4/2018 | 5/6/2018 | P | FAIL |
Daryl DeGrange
|
|
|
Thanks James, give me a call if you have any questions. -Aaron ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting NEC 110.14 Electrical connection of array equipment grounding conductor not porperly terminated in house panel. Several strands not in chair lug.
|
Final | 4/25/2018 | 4/27/2018 | 4/25/2018 | A | CANC |
James Ady
|
|
|
Todd, owner will be there. Phone #: ###-#### >> Inspection requested via web by BRS Permitting Inspection cancelled from web by: BRS Permitting
|
Electrical Rough-In | 4/19/2018 | 4/20/2018 | 4/20/2018 | A | PASS |
James Ady
|
|
|
Kyle and crew will be there in the AM Phone #: ###-#### Inspection requested via web by BRS Permitting Listing only ok
|
Issue PAID IN FULL permit | | | 3/23/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Telephone call | | | 3/23/2018 | | DONE |
|
|
|
Contacted company to remind them this permit hasnt been paid for yet and to see if they are still doing the work.
|
Application received | | | 3/19/2018 | | DONE |
|
|
|
This permit was created on the web by BRS Permitting
|