Permit Information
Permit NumberELE18-01092
StatusFinaled
Name POWERHOUSE ELECTRIC
Site Address 6931 E GREYBULL DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: new home
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/27/20186/28/20186/28/2018APASS
DetailsRock A. Hudson
garage code 2124 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
Rough-In Permanent Service3/28/20183/29/20183/29/2018APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made rough in ok p/s u/g n ok
Rough-In Permanent Service3/27/20183/28/20183/28/2018AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.3- Installation not complete. Missed recessed con in kitchen area.
314.25- Recessed can junction box covers shall be installed to totally enclose box. Upstairs can back cover not installed as per manufacturers instructions.
300.4- Nail plates needed in kitchen under switch.
WUI zone A- Outdoor recessed con fire barriers not complete at time of inspection.
Issue PAID IN FULL permit  3/23/2018 DONE
Payment received via Govolutions
Application received  3/23/2018 DONE
This permit was created on the web by Darryn Coburn