Final | 7/11/2018 | 7/12/2018 | 7/12/2018 | A | PASS |
Tom Saunders
|
|
|
Building H, access 6935 Phone #: ###-#### Inspection requested via web by David Nelson...coprrections made...ok to final
|
Final | 7/11/2018 | 7/11/2018 | 7/11/2018 | P | FAIL |
Tom Saunders
|
|
|
access 6935 Phone #: ###-#### Inspection requested via web by David Nelson... unit 1..abrasion protection needs added for romex at bedroom heaters unit 2..romex protection-heaters outlets shall not be installed above heater unit 3..romex protection-heaters outlets shall not be installed above heater unit 4 romex protection-heaters outlets shall not be installed above heater unit 5..abrasion protection for romex living heater unit 6..patio light not working romex protection-heaters unit 7..living rm heater-junction cover kitchen outlets need to be completed panel needs labelled completely unit 8..panel needs labelled completely
|
Rough-In Permanent Service | 3/29/2018 | 3/29/2018 | 3/29/2018 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson...rough ok to cover...p/s, u/g, 2 meter packs, 9 meters, new feeds from transformer needed
|
Rough-In Permanent Service | 3/27/2018 | 3/28/2018 | 3/28/2018 | A | FAIL |
Tom Saunders
|
|
|
electrical rewire after fire, building H units 1,2,3,4,5,6,8 Phone #: ###-#### Inspection requested via web by David Nelson...
H8-wires need stapled 1 1/4 back fromface of stud where sheetrock cut out, nail plates at panel H6- bushing on pipe with feeder wires H5- nail plates in ceiling H2- finish wiring for outside light, misc outlets need made up, wires need stapled 1 1/4 back from face of stud 12/2 living rm H3- exhaust fan wiring needs completed in bath nail plates needed on sub feed at panel
listed connector at service going from PVC to HUB...both meter packs
|
Issue PAID IN FULL permit | | | 3/27/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/27/2018 | | DONE |
|
|
|
This permit was created on the web by David Nelson
|
First Notice | 7/12/2018 | 7/12/2018 | | | |
Tom Saunders
|
|
|
|