Final | 7/25/2018 | 7/26/2018 | 7/26/2018 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
Fees Due Hold | 7/26/2018 | | 7/26/2018 | | DONE |
|
|
|
|
Final | 7/25/2018 | 7/25/2018 | 7/25/2018 | P | FAIL |
James Ady
|
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Darryn Coburn Master bed lights, receps and closet light dead. 3rd floor bar receps dead
|
Final | 7/24/2018 | 7/25/2018 | 7/25/2018 | A | FAIL |
Rock A. Hudson
|
|
|
4324 Garage Code Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Not all circuits operating, upper level stair not working and upper landing. Buried box. 250.148- Where conductors are spliced in a box all equipment grounds shall be connected together by approved means. Island 3 gang. 314.17- Where NM cable enters a non metallic box the sheathing shall enter box a minimum of 1/4". Island 3 gang. 314.20- Where box is mounted in a combustible material it shall be flush or have extension rings installed. *Job not checked out prior to inspection, reinspection fee assessed.
|
Reinspection Fee (no hold) | 7/25/2018 | 7/25/2018 | 7/25/2018 | P | PASS |
Rock A. Hudson
|
|
|
4324 Garage Code Phone #: ###-#### Inspection requested via web by Darryn Coburn Reinspection fee assessed due to job not checked out prior to calling for inspection.
|
Rough-In Permanent Service | 4/3/2018 | 4/3/2018 | 4/3/2018 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough in ok p/s u/g n ok
|
Issue PAID IN FULL permit | | | 3/29/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/29/2018 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|