Final | 6/28/2018 | 6/28/2018 | 6/28/2018 | P | PASS |
Tom Saunders
|
|
|
garage code 2018 Phone #: ###-#### Inspection requested via web by Darryn Coburn..ok to final
|
Final | 6/27/2018 | 6/27/2018 | 6/27/2018 | P | FAIL |
Rock A. Hudson
|
|
|
garage code 2018 Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.70(A)- A single lighting outlet required for habitable rooms shall be connected to a lamp holder or luminaire. Family room has a remote control paddle fan with out a lamp holder or luminaire installed. 356.30-LFNC shall be secured in place at AC unit.
|
Rough-In Permanent Service | 4/16/2018 | 4/17/2018 | 4/17/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 4/13/2018 | 4/16/2018 | 4/16/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.52(A)- A receptacle outlet shall be installed within 6' of a door. Up bed across from top of stair between entrance door and closet door 10' of wall with no receptacle.
|
Issue PAID IN FULL permit | | | 4/5/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/5/2018 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|