Final | 6/14/2018 | 6/15/2018 | 6/15/2018 | A | PASS |
Rock A. Hudson
|
|
|
Access code 3535 Phone #: ###-#### Inspection requested via web by Paula Gratiot Final ok
|
Final | 6/14/2018 | 6/14/2018 | 6/14/2018 | P | FAIL |
Rock A. Hudson
|
|
|
access code 3535 Phone #: ###-#### Inspection requested via web by Paula Gratiot 110.3- Entry hall 3way, 4way, 3way will not operate with 4 way in either position. 110.3- Christmas GFCI will not trip when tested. 210.12- Office has a closet with a clothes rod and shall have AFCI protection.
|
Rough-In Permanent Service | 4/9/2018 | 4/10/2018 | 4/10/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Paula Gratiot Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 4/9/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/9/2018 | | DONE |
|
|
|
This permit was created on the web by Paula Gratiot
|