Permit Information
Permit NumberELE18-01403
StatusFinaled
Name PACIFIC SOURCE ELECTRIC LLC
Site Address 2207 W OVERLAND RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Alternations to several lighting and outlets.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice8/6/20188/6/20189/7/2018 DONE
DetailsRock A. Hudson
This permit finaled on the web by Harvey Reyna
Final8/2/20188/6/20188/6/2018APASS
DetailsRock A. Hudson
Contact for Entry into building: Rex Neilson ###-#### Phone #: ###-#### Inspection requested via web by Harvey Reyna
Kitchen area to be permitted and finished in future. Final ok
Electrical Rough-In5/25/20185/29/20185/29/2018APASS
DetailsEric Story
Ceiling in kitchen area. Phone #: ###-#### Inspection requested via web by Harvey Reyna
Ceiling only in kitchen ok to cover suspended ceilings tiles
Electrical Rough-In4/16/20184/17/20184/17/2018APASS
DetailsRock A. Hudson
soffit inspection Phone #: ###-#### Inspection requested via web by Harvey Reyna
Access required to soffit due to junction boxes above. Shall provide access to boxes at each end that face out for face of soffit. Front soffit only rough in ok cover
Conference4/12/20184/12/20184/12/2018PDONE
DetailsRock A. Hudson
Contact: Dave Phone #: ###-#### Inspection requested via web by Harvey Reyna
Discussed location of panels, what wiring ok to remain, show window receptacles, inspections needed.
240.24(C)- Panel location in kitchen area shall have adequate distance from sink for a barrier providing separation.
240.24(E)- Panel located in bathroom may remain if enclosed with walls and a doorway creating separation. Also noted in BCC 4-05-31(A).
210.62- Show window receptacles shall be located with in 18" of top of window and spacing corrected.
400.12- Asked if existing light fixtures could remain. Flexible cords shall not be used as substitute for structural wiring. Lighting shall comply with IECC for total wattage allowed.
Asked if could request a inspection for certain areas to be done in phases to help job move forward quicker. OK to request couple extra inspections.
Issue PAID IN FULL permit  4/11/2018 DONE
Payment received via Govolutions
Owner Supplied Equipment  4/11/2018  
Application received  4/11/2018 DONE
This permit was created on the web by Harvey Reyna