Final | 4/23/2018 | 4/24/2018 | 4/24/2018 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan...ok to final
|
Rough-In Permanent Service | 4/19/2018 | 4/20/2018 | 4/19/2018 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan...p/s u/g reconnect ok
|
Issue PAID IN FULL permit | | | 4/16/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/16/2018 | | DONE |
|
|
|
This permit was created on the web by steve ragan
|