Final | 7/5/2018 | 7/5/2018 | 7/5/2018 | P | PASS |
Rock A. Hudson
|
|
|
Door code is 9876 if needed Phone #: ###-#### Inspection requested via web by Ron Zimmerman Final ok
|
Final | 7/3/2018 | 7/3/2018 | 7/3/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman 210.8- All receptacles located in kitchen area shall have GFCI protection. Pizza oven, and 120 volt receptacles
|
Electrical Rough-In | 6/14/2018 | 6/14/2018 | 6/14/2018 | A | PASS |
Mark Moncarr
|
|
|
one additional room needs inspection Phone #: ###-#### Inspection requested via web by Ron Zimmerman Ok cover new wall addition upon entry.
|
Electrical Rough-In | 6/12/2018 | 6/12/2018 | 6/12/2018 | A | PASS |
James Ady
|
|
|
door code is 9876 if no one is there Phone #: ###-#### Inspection requested via web by Ron Zimmerman Corrections made rough in ok walls only
|
Electrical Rough-In | 6/11/2018 | 6/11/2018 | 6/11/2018 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman Handy boxes on back column over filled. (10.3 cu in.) 2 12-2mc =15.75 min.
|
Electrical Rough-In | 4/28/2018 | 4/30/2018 | 4/30/2018 | A | PASS |
Rock A. Hudson
|
|
|
inspection for short wall and wall behind short wall Phone #: ###-#### Inspection requested via web by Ron Zimmerman Service area walls only rough in ok cover
|
Issue PAID IN FULL permit | | | 4/28/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 4/28/2018 | | |
|
|
|
|
Application received | | | 4/28/2018 | | DONE |
|
|
|
This permit was created on the web by Ron Zimmerman
|