Temporary Service | 5/8/2018 | 5/9/2018 | 5/9/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by ERIC CENTERS t/s u/g n ok
|
Issue PAID IN FULL permit | | | 5/7/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/7/2018 | | DONE |
|
|
|
This permit was created on the web by ERIC CENTERS
|