Final | 5/15/2018 | 5/15/2018 | 5/15/2018 | P | PASS |
Mark Moncarr
|
|
|
Fuses changed to match unit rating Phone #: ###-#### Inspection requested via web by Jake Cutler Corrections made. Final for both A/C units. 1 on the E side, and 1 on the NW corner.
|
Final | 5/9/2018 | 5/9/2018 | 5/9/2018 | P | FAIL |
Tom Saunders
|
|
|
Split heating cooling units Phone #: ###-#### Inspection requested via web by Jake Cutler...OCP sized too large as per manufacturer's specs...30A fuses installed need to be no larger than 25A
|
Issue PAID IN FULL permit | | | 5/9/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/9/2018 | | DONE |
|
|
|
This permit was created on the web by Jake Cutler
|