Final | 8/10/2018 | 8/10/2018 | 8/10/2018 | P | PASS |
James Ady
|
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn final ok
|
Rough-In Permanent Service | 6/4/2018 | 6/4/2018 | 6/4/2018 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 5/31/2018 | 6/1/2018 | 6/1/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn 210.52- No point measured a along floor line shall exceed 6' from a receptacle outlet. Dining room. 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage. Nail plates needed level 3 lower plate under switch and level 1 above entry switches. 314.25- Rcess junction box cover not tight to box on level 2
|
Issue PAID IN FULL permit | | | 5/10/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/10/2018 | | DONE |
|
|
|
This permit was created on the web by Bob Glenn
|