Temporary Service | 6/6/2018 | 6/7/2018 | 6/7/2018 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn corrections made T/S ok
|
Temporary Service | 6/6/2018 | 6/6/2018 | 6/6/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Temp service energized. Stopped to check GFCI protection. 590.6(B)- Receptacles other than 120 volt used for temp power shall have GFCI protection. 250 did not trip when tested.
|
Change Status to I | | | 6/6/2018 | | DONE |
|
|
|
reopen per Rock
|
Temporary Service | 5/23/2018 | 5/23/2018 | 5/23/2018 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
Issue PAID IN FULL permit | | | 5/23/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/23/2018 | | DONE |
|
|
|
This permit was created on the web by Bob Glenn
|