Permit Information
Permit NumberELE18-02181
StatusFinaled
Name A & B ELECTRIC INC
Site Address 5390 W IRVING ST
Project Name 
Customer Number1755
ePlanReviewNo
Description
New: Electrical scope for new shop
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Print Statement  8/15/2019 DONE
Final1/29/20191/30/20191/30/2019APASS
DetailsEric Story
Re-inspect for final. Phone #: ###-#### Inspection requested via web by Bryan Atkins
Occ card not on site
Corrections fixed final ok
Conference1/30/20191/30/20191/30/2019APASS
DetailsRock A. Hudson
After discussing building type use, as per Daryl DeGrange GFCI protectoin of two 50 amp receptacles not required
Final1/24/20191/25/20191/25/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Bryan Atkins
110.3- GFCI on north wall will not trip.
210.8- Single phase up to 50 amp and 3- phase receptacles up to 100 amp 150 volts to ground or less shall have GFCI protection. Welder and plasma.
330.30- MC cable shall be secured with in 12" of boxes other than fixture whips. North door opener.
400.5- 6-3 flexible cords with 3 current carrying conductors ampacity shall not exceed 45 amps. Welder and plasma.
400.12- Flexible cords shall not be run thru walls, floors, or ceilings. Remove temp lighting cords and one cord from level 1 to mezz for fan.
Electrical Rough-In12/10/201812/11/201812/11/2018APASS
DetailsEric Story
Rough-in under mezzanine Phone #: ###-#### Inspection requested via web by Bryan Atkins
Mezzanine only ok to cover conduit in hard lid, remaining to be surface mounted....
Electrical Rough-In11/2/201811/2/201811/2/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Bryan Atkins
Bathroom rough in ok cover
Permanent Service10/18/201810/19/201810/19/2018AFAIL
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Bryan Atkins
120.24 AFC calc required proir to service being energized
Electrical Rough-In9/28/201810/1/201810/1/2018APASS
DetailsRock A. Hudson
Electrical Underground Rough-In Phone #: ###-#### Inspection requested via web by Bryan Atkins
Underground 2- 1" from building to gate rough in ok cover
Electrical Rough-In6/26/20186/26/20186/26/2018PPASS
DetailsTom Saunders
Uffer Ground Phone #: ###-#### Inspection requested via web by Bryan Atkins...ok to cover
Electrical Rough-In6/12/20186/13/20186/13/2018APASS
DetailsEric Story
Underground Phone #: ###-#### Inspection requested via web by Bryan Atkins
u/g ok to cover
Electrical Rough-In6/11/20186/12/20186/12/2018AFAIL
DetailsEric Story
Underground secondary and security gate. Phone #: ###-#### Inspection requested via web by Bryan Atkins
u/g needs to be 24"
Issue PAID IN FULL permit  6/11/2018 DONE
Payment received via Govolutions
Application received  6/11/2018 DONE
This permit was created on the web by Bryan Atkins
First Notice1/30/20191/30/2019   
DetailsEric Story