Final | 9/12/2018 | 9/12/2018 | 9/12/2018 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Hidajet Zahic fInal ok
|
Rough-In Permanent Service | 6/19/2018 | 6/19/2018 | 6/19/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Hidajet Zahic Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 6/18/2018 | 6/19/2018 | 6/19/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Hidajet Zahic 110.3- Unable to confirm listing for non-metallic pancake boxes on exterior. Provde documentation. 210.52- A receptacle outlet shall be located with in 6' of flex room door to patio. nearest one 8'. 300.4 (A)(1)- Cables passing thru holes that do not meaintain 1 1/4" from framing surface they shall be protected from damage by nail plates. Marked with X. 300.4 (B)(1)- Where NM cable enter fireplace it shall be protected by a bushd fitting. 300.4(G)- Where #4 or larger enter an enclosure they shall enter thru a bushed fitting. Check smoke detector locations, unable to locate print to confirm. complete make-up, fireplace switches, wirenuts missing switch near office stair.
|
Issue PAID IN FULL permit | | | 6/18/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/18/2018 | | DONE |
|
|
|
This permit was created on the web by Hidajet Zahic
|