ELE-Aging Inspection | 7/10/2020 | 7/10/2020 | 7/13/2020 | | DONE |
Daryl DeGrange
|
|
|
see final
|
Final | 7/13/2020 | 7/13/2020 | 7/13/2020 | A | PASS |
Daryl DeGrange
|
|
|
Conference meeting complete, final ok
|
Electrical Rough-In | 4/19/2019 | 4/22/2019 | 4/22/2019 | A | CANC |
Eric Story
|
|
|
Please call Joe 30 min prior @ ###-#### for access if you would, Thx so much! Steve,BPL Phone #: ###-#### Inspection requested via web by Steven Meredith Permit issues exist Multiple violations exist Supporting of NM cables with no support or to close framing Bonding in sub panels need removed and seperating of grounded and grounding conductors
|
Conference | 6/21/2018 | 6/22/2018 | 6/22/2018 | A | DONE |
Mark Moncarr
|
|
|
thanks for meeting me on this Marc, see ya at 8:30....Steve Phone #: ###-#### Inspection requested via web by Steven Meredith Discussed outlet layout up, down and basement. Some KO's needed in various areas.
|
Issue PAID IN FULL permit | | | 6/21/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/21/2018 | | DONE |
|
|
|
This permit was created on the web by Steven Meredith
|