Final | 7/26/2018 | 7/27/2018 | 7/27/2018 | A | PASS |
Mark Moncarr
|
|
|
Final Inspection for Maverik speed oven circuit Contact Matt Hannum Thank you, Phone #: ###-#### Inspection requested via web by Tom Betty Correction made. New speed oven installed is hardwired with brkr lockout.
|
Final | 6/28/2018 | 6/29/2018 | 6/29/2018 | P | CANC |
Tom Saunders
|
|
|
Final Re-inspection. Contact Matt Hannum Thank you, Phone #: ###-#### >> Inspection requested via web by Tom Betty Inspection cancelled from web by: Tom Betty
|
Final | 6/28/2018 | 6/28/2018 | 6/28/2018 | P | FAIL |
Tom Saunders
|
|
|
Final for circuit for new speed oven. Contact Matt Hannum Thank you, Phone #: ###-#### Inspection requested via web by Tom Betty...
all receptacles shall have GFCI protection in kitchen...210.8(B)
|
Issue PAID IN FULL permit | | | 6/27/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 6/27/2018 | | |
|
|
|
|
Application received | | | 6/27/2018 | | DONE |
|
|
|
This permit was created on the web by Tom Betty
|
First Notice | 7/27/2018 | 7/27/2018 | | | |
Mark Moncarr
|
|
|
|