First Notice | 7/20/2018 | 7/20/2018 | 12/5/2018 | | DONE |
Tom Saunders
|
|
|
This permit finaled on the web by Rick Beckman
|
Final | 7/20/2018 | 7/20/2018 | 7/20/2018 | P | PASS |
Tom Saunders
|
|
|
Rick Phone #: ###-####...corrections made...ok to final
|
Final | 7/19/2018 | 7/20/2018 | 7/20/2018 | A | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Rick Beckman... 1..OCPD for mini split need sized to nameplate rating...max 15A 2..outlets in shop area no power 110.7 3..panel shall be clearly and legible labelled all circuits in panel 4..all outlets in back warehouse shall have GFCI protection..4 SQ @ panel 210.8(B)
|
Electrical Rough-In | 7/10/2018 | 7/11/2018 | 7/11/2018 | A | PASS |
Tom Saunders
|
|
|
rough-in of 2 offices and some wiring on west wall of deck plus north and west wall in warehouse, Thanks Phone #: ###-#### Inspection requested via web by Rick Beckman...rough ok to cover...verify breaker l/o or disconnect on water heater at final
|
Issue PAID IN FULL permit | | | 7/2/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 7/2/2018 | | |
|
|
|
|
Application received | | | 7/2/2018 | | DONE |
|
|
|
This permit was created on the web by Rick Beckman
|