Final | 8/29/2018 | 8/30/2018 | 8/30/2018 | A | PASS |
Tom Saunders
|
|
|
code is the address Phone #: ###-#### Inspection requested via web by Neal Rumsey... corrections made ok to final
|
Final | 8/29/2018 | 8/29/2018 | 8/29/2018 | A | FAIL |
Tom Saunders
|
|
|
code 7920 Phone #: ###-#### Inspection requested via web by Neal Rumsey....
1..panel screws missing-110.12, 110.3 2..A/C whip needs strapps installed 3..breaker for hot tub needs installed for verification-110.3 4..mst bath exhaust fan shall have GFCI protection-in foot print of shower-210.8,110.3 5..no power in upstairs bedroom..missing outlet-110.7 6..hall lights-boxes recessed more then 1/4" box extensions or spark rings needed
|
Rough-In Permanent Service | 7/8/2018 | 7/9/2018 | 7/9/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Neal Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 7/8/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/8/2018 | | DONE |
|
|
|
This permit was created on the web by Neal Rumsey
|