Final | 7/30/2019 | 7/30/2019 | 7/30/2019 | P | PASS |
Eric Story
|
|
|
Contact: Caleb Burke Phone #: ###-#### Inspection requested via web by Deb Gooden Occ card signed
|
Electrical Rough-In | 4/22/2019 | 4/23/2019 | 4/23/2019 | P | PASS |
Eric Story
|
|
|
Contact: Caleb Burke Phone #: ###-#### Inspection requested via web by Deb Gooden Weight training area walls only ok to cover
|
Electrical Rough-In | 4/16/2019 | 4/17/2019 | 4/17/2019 | P | PASS |
Eric Story
|
|
|
Contact: Caleb Burke. Ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Hallway celing and U/G to fence ok to cover
|
Final | 2/14/2019 | 2/15/2019 | 2/15/2019 | A | NR |
Rock A. Hudson
|
|
|
CONTACT: CALEB BURKE Phone #: ###-#### Inspection requested via web by Deb Gooden Called contact and they stated commissioning reports are not complete on lighting control and energy measurement devices with remote communication yet. Will complete and recall.
|
Electrical Rough-In | 2/1/2019 | 2/4/2019 | 2/4/2019 | A | PASS |
Eric Story
|
|
|
CALL CALEB BURKE ON SITE ###-#### CEILING GRID INSPECTION Inspection requested via web by Deb Gooden Ceiling in Phase 3 only ok to cover
|
Electrical Rough-In | 12/11/2018 | 12/12/2018 | 12/12/2018 | A | PASS |
Eric Story
|
|
|
Contact: Caleb Burke Phone #: ###-#### Inspection requested via web by Deb Gooden Dormitories walls only ok to cover
|
Electrical Rough-In | 11/13/2018 | 11/14/2018 | 11/14/2018 | A | PASS |
Eric Story
|
|
|
CONTACT: CALEB BURKE underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden U/G to street lights and grounding of cages ok to cover
|
Final | 10/19/2018 | 10/19/2018 | 10/19/2018 | P | PART |
Eric Story
|
|
|
As per Electrical Engineer area has been de-classified as a hazardous area and is ok to occupy this garage at this time..
|
Final | 10/16/2018 | 10/17/2018 | 10/17/2018 | A | CANC |
Eric Story
|
|
|
CONTACT NAME CALEB BURKE RE INSPECTION FOR FINAL THANK YOU Phone #: ###-#### Inspection requested via web by Deb Gooden Still waiting on area of classification
|
Final | 10/15/2018 | 10/16/2018 | 10/16/2018 | P | PART |
Eric Story
|
|
|
Contact name will be Caleb Burke Phone #: ###-#### Inspection requested via web by Deb Gooden Kitchen area only ok at this time, Garage area is need of area of classification from a licensed engineer to determine if air exchange unit is sufficient to move particals away
|
Permanent Service | 9/7/2018 | 9/11/2018 | 9/11/2018 | A | PASS |
Eric Story
|
|
|
On site contact name will be Caleb Burke, his number is ###-####. Thank you Phone #: ###-#### Inspection requested via web by Deb Gooden Bonding and grounding completed AFC calc is 9914 p/s u/g n ok
|
Permanent Service | 9/5/2018 | 9/7/2018 | 9/7/2018 | A | PASS |
James Ady
|
|
|
Contact: Dan Schmidt, may be ###-#### Phone #: ###-#### Inspection requested via web by Deb Gooden Will call for a am inspection Tues. 9/11/18 to Verify grounding. p/s u/g n ok
|
Electrical Rough-In | 8/24/2018 | 8/24/2018 | 8/24/2018 | P | PASS |
Eric Story
|
|
|
Contact: Caleb Burke. Ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Sun roo ok to cover
|
Electrical Rough-In | 7/26/2018 | 7/26/2018 | 7/26/2018 | P | PASS |
Eric Story
|
|
|
Contact: Caleb Burke Phone #: ###-#### Inspection requested via web by Deb Gooden Hard lids ok to cover in PPe closet and 104
|
Issue PAID IN FULL permit | | | 7/9/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/9/2018 | | DONE |
|
|
|
This permit was created on the web by Deb Gooden
|
First Notice | 7/30/2019 | 7/30/2019 | | | |
Eric Story
|
|
|
|