First Notice | 8/6/2018 | 8/6/2018 | 8/20/2018 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by David Feller
|
Final | 8/6/2018 | 8/6/2018 | 8/6/2018 | P | PASS |
Rock A. Hudson
|
|
|
Reinspect for data wire off ceiling grid Several open electrical J Boxes contact Lance ###-#### if need assistance to excess space. Phone #: ###-#### Inspection requested via web by David Feller Final ok
|
Electrical Rough-In | 8/6/2018 | 8/6/2018 | 8/6/2018 | P | PASS |
Rock A. Hudson
|
|
|
Reinspect for data wire off ceiling grid Several open electrical J Boxes contact Lance ###-#### if need assistance to excess space. Phone #: ###-#### Inspection requested via web by David Feller Grid rough in ok cover
|
Final | 7/31/2018 | 8/1/2018 | 8/1/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Call Lance for access to space if not open 208.703.2035 Phone #: ###-#### Inspection requested via web by David Feller BCC 4-05-32- No code violation shall be retained. 300.11- Misc cables shall be supported independant of grid. 314.25- All boxes containing a splice shall have covers. 3 open boxes near front of space. All device covers off for painting.
|
Electrical Rough-In | 7/16/2018 | 7/17/2018 | 7/17/2018 | A | PASS |
Rock A. Hudson
|
|
|
New office wall cover Outlets on existing wall fished in. Contact Lance for door access if job is locked up. Phone #: ###-#### Inspection requested via web by David Feller Wall rough in ok cover
|
Issue PAID IN FULL permit | | | 7/16/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/16/2018 | | DONE |
|
|
|
This permit was created on the web by David Feller
|