Final | 8/8/2018 | 8/9/2018 | 8/9/2018 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Kelly Tarter Job complete, Final ok
|
Permanent Service | 7/27/2018 | 7/30/2018 | 7/30/2018 | P | PASS |
Rock A. Hudson
|
|
|
Please call Brandon 45 min before inspection.
Thanks Phone #: ###-#### Inspection requested via web by Kelly Tarter 46k previously stated is value at transformer. 15,900 value posted. p/s u/g rec ok
|
Permanent Service | 7/23/2018 | 7/23/2018 | 7/23/2018 | P | FAIL |
Rock A. Hudson
|
|
|
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Over 46K available at terminal of existing main breaker. Will create change order to correct.
|
Issue PAID IN FULL permit | | | 7/19/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/19/2018 | | DONE |
|
|
|
This permit was created on the web by Kelly Tarter
|
First Notice | 8/9/2018 | 8/9/2018 | | | |
Daryl DeGrange
|
|
|
|