Final | 10/11/2018 | 10/11/2018 | 10/11/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake Final ok
|
Final | 9/25/2018 | 9/26/2018 | 9/26/2018 | A | PART |
Daryl DeGrange
|
|
|
Chris ###-#### TCO bar and sitting area. Partial final OK
|
Final | 9/25/2018 | 9/25/2018 | 9/25/2018 | P | PART |
Rock A. Hudson
|
|
|
TCO for bar and sitting area ###-#### Chris. South east side of bar unable to provide GFCI protection for receptacles located on back side for mobile devices and 1 inside bar receptacle due to wiring method used. If unable to GFCI area needed these circuits shall be locked out until compliant with NEC. Bar needs to open evening of 9-25-18. Contractor agrees to complete or lock out. TCO ok
|
Final | 9/25/2018 | 9/25/2018 | 9/25/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Partial final bar area please call Chris 9411710 prior to inspection Phone #: ###-#### Inspection requested via web by Ryan Wake 210.8- All 20 amp 120 volt receptacle outlets located within 6' of a sink shall have GFCI protection. GFCI devices shall be installed in a readily accessible location. Receptacles behind appliances and on back side of bar for charging mobile devices.
|
Electrical Rough-In | 9/14/2018 | 9/14/2018 | 9/14/2018 | P | PASS |
Rock A. Hudson
|
|
|
Bar rough in inspection Phone #: ###-#### Inspection requested via web by Ryan Wake Bar wall rough in ok cover
|
Electrical Rough-In | 8/16/2018 | 8/17/2018 | 8/17/2018 | A | PASS |
Rock A. Hudson
|
|
|
Rough in front entry Phone #: ###-#### Inspection requested via web by Ryan Wake Entrance walls and hardlid and cloud rough in ok cover
|
Electrical Rough-In | 8/15/2018 | 8/16/2018 | 8/16/2018 | A | PASS |
Rock A. Hudson
|
|
|
Chris is contact. Partial rough in walls and ceiling in lobby. Phone #: ###-#### Inspection requested via web by Ryan Wake Columns, misc walls and patches, fireplace wall rough in ok cover
|
Electrical Rough-In | 8/13/2018 | 8/14/2018 | 8/13/2018 | A | PASS |
Daryl DeGrange
|
|
|
Chris is contact. Ceiling inspection Phone #: ###-#### Inspection requested via web by Ryan Wake Rough-in ok cover hard lid above restaurant area only
|
Electrical Rough-In | 8/8/2018 | 8/9/2018 | 8/9/2018 | P | PASS |
Daryl DeGrange
|
|
|
Rough in dining walls only Inspection requested via web by Ryan Wake rough-in ok cover
|
Electrical Rough-In | 8/3/2018 | 8/3/2018 | 8/3/2018 | P | PASS |
Rock A. Hudson
|
|
|
Please call before inspection as I will be in and out. Porte Corche rough in Phone #: ###-#### Inspection requested via web by Ryan Wake Ceiling noted rough in ok cover
|
Issue PAID IN FULL permit | | | 7/23/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 7/23/2018 | | |
|
|
|
|
Application received | | | 7/23/2018 | | DONE |
|
|
|
This permit was created on the web by Ryan Wake
|
First Notice | 10/11/2018 | 10/11/2018 | | | |
Rock A. Hudson
|
|
|
|