Final | 9/26/2018 | 9/27/2018 | 9/27/2018 | A | PASS |
Daryl DeGrange
|
|
|
ACCESS CODE 1122 Phone #: ###-#### Inspection requested via web by Eric Schroeder corection done, final ok
|
Rough-In Permanent Service | 7/26/2018 | 7/30/2018 | 7/30/2018 | A | PASS |
Tom Saunders
|
|
|
ACCESS CODE 1122 Phone #: ###-#### Inspection requested via web by Eric Schroeder... rough ok to cover-corrections made p/s u/g reconnect ok
|
Rough-In Permanent Service | 7/25/2018 | 7/26/2018 | 7/26/2018 | A | FAIL |
Rock A. Hudson
|
|
|
ACCESS CODE 1122 Phone #: ###-#### Inspection requested via web by Eric Schroeder 110.14- Dissimilar metals shall not be spliced together. Range junction box garage ceiling. 300.15- NM cables shal terminate in a box. 12-3 HR and others hanging from utility ceiling.
|
Issue PAID IN FULL permit | | | 7/25/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/25/2018 | | DONE |
|
|
|
This permit was created on the web by Eric Schroeder
|