Final | 2/21/2019 | 2/22/2019 | 2/22/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Brecklee Brown Corections made final ok
|
Final | 1/23/2019 | 1/24/2019 | 1/24/2019 | A | CANC |
Tom Saunders
|
|
|
Jeff Powell will meet you on site if you can call when you are on your way ###-#### Phone #: ###-#### >> Inspection requested via web by Brecklee Brown Inspection cancelled from web by: Brecklee Brown
|
Final | 9/27/2018 | 9/28/2018 | 9/28/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Plans have been left on site in the meter box Phone #: ###-#### Inspection requested via web by Ashley White 310.15(B)(7)(2)- For feeders supplying entire load associated with a single family dwelling they shall be permitted to have an ampacity not less than 83% of service rating. 200X83%= 166 amps. 75 degree column 2/0 minimum required 1/0 installed. 358.42 EMT connectors shall be made tight. * Plans shall be provided as stated in notes. None on site.
|
Electrical Rough-In | 9/13/2018 | 9/18/2018 | 9/18/2018 | P | CANC |
Eric Story
|
|
|
Please call Brian when you are on your way, he is the foreman on site ###-#### Phone #: ###-#### Inspection requested via web by Ashley White
|
Electrical Rough-In | 9/13/2018 | 9/18/2018 | 9/18/2018 | A | PASS |
Eric Story
|
|
|
Please call Brian when you are on your way, he is the foreman on site ###-#### Phone #: ###-#### Inspection requested via web by Ashley White Verified U/L listing and scope of work for solar array
|
Issue PAID IN FULL permit | | | 7/31/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/31/2018 | | DONE |
|
|
|
This permit was created on the web by Ashley White
|