Final | 11/7/2018 | 11/7/2018 | 11/7/2018 | A | PASS |
James Ady
|
|
|
GARAGE CODE 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
Rough-In Permanent Service | 8/29/2018 | 8/29/2018 | 8/29/2018 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 8/27/2018 | 8/28/2018 | 8/28/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn 110.3- Recessed can junction box covers shall be installed as per instructions. Covers shall be tight to boxes. Kitchen and over stair landing. 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage. Kitchen island, 2 in garage, front rm, 3 level 2 hall. 300-14- Minimum of 6" of free conductor shall be present at each outlet. 2 receptacles in front room no free conductor on equipment grounds
|
Issue PAID IN FULL permit | | | 8/13/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/13/2018 | | DONE |
|
|
|
This permit was created on the web by Bob Glenn
|