Final | 8/27/2018 | 8/28/2018 | 8/28/2018 | A | PASS |
Tom Saunders
|
|
|
call 30 mins ahead-Clark Phone #: ###-####...finalling out permit...work was done and corrections made by Electrical contractor permit number ELE18-03280
|
Final | 8/23/2018 | 8/24/2018 | 8/24/2018 | A | FAIL |
Tom Saunders
|
|
|
Call ahead for access - Randy Phone #: ###-####...
wiring complete with no inspection in upstairs living unit with bathroom, kitchen, and sleeping area
requiring an Electrical contractor be hired to inspect, bring up to code, and take responsibility for wiring done by others 1) wiring will be verified to meet electrical code of 2007 2) downstairs panel shall be properly labelled for each circuit of upstairs unit 3) GFCI protection shall be brough up to code 4) AFCI protection shall be brough up to code
|
Issue PAID IN FULL permit | | | 8/23/2018 | | DONE |
|
|
|
|
Application received | | | 8/14/2018 | | |
|
|
|
|