Final | 8/31/2018 | 8/31/2018 | 8/31/2018 | P | PASS |
Rock A. Hudson
|
|
|
AC unit to have seperate permit. Bushing installed. Final ok
|
Final | 8/31/2018 | 8/31/2018 | 8/31/2018 | P | FAIL |
Rock A. Hudson
|
|
|
200 amp existing pedestal Phone #: ###-#### Inspection requested via web by jamie berg 300.4(G)- Conduits containing #4 or larger conductors shall have a bushing installed to protect conductors from damage. 2" at pedistal. 334.12(B)(4)- NM cable shall not be installed in a wet or damp location. AC sitting on lot with 10-2 NM cable installed in flexible conduit to AC unit.
|
Permanent Service | 8/31/2018 | 8/31/2018 | 8/31/2018 | P | PASS |
Rock A. Hudson
|
|
|
200 amp existing pedestal Phone #: ###-#### Inspection requested via web by jamie berg p/s u/g rec ok
|
Issue PAID IN FULL permit | | | 8/20/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/20/2018 | | DONE |
|
|
|
This permit was created on the web by jamie berg
|