Permit Information
Permit NumberELE18-03193
StatusFinaled
Name D & M ELECTRIC
Site Address 12877 W GRENADIER DR
Project Name 
Customer Number82118
ePlanReviewNo
Description
Addition: Install feeder, sub panel & circuits for addition
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/9/201810/10/201810/10/2018APASS
DetailsDaryl DeGrange
Fixed Tub wire connections. Phone #: ###-#### Inspection requested via web by Douglas Hackney Swim hot tub in location within new addition to comply with required clearances for receptacles at time of final inspection, Hot tub on wheels. ceiling fan removed and planked off. Non conductive barrier between tub and exhaust fan. final ok
Final10/7/201810/8/201810/8/2018AFAIL
DetailsDaryl DeGrange
Code correction fixed
Install GFCI breaker in sub panel for lighting. Phone #: ###-#### Inspection requested via web by Douglas Hackney NEC 314.4 Metal boxes shall be grounded and bonded Exposed conductors at point of entry of pool heater shall be relocated to inside of heater enclosure.
Final10/5/201810/5/201810/5/2018PFAIL
DetailsEric Story
Trim Out - Final
Go thru gate on side. New addition will be open. Phone #: ###-#### Inspection requested via web by Douglas Hackney
Lights above pool shall be GFCI not AFCI protected
Electrical Rough-In8/24/20188/27/20188/27/2018APASS
DetailsTom Saunders
Code corrections fixed. Relocated outlet to outside. Pool to be moved for proper clearance from all other electrical boxes. Phone #: ###-#### Inspection requested via web by Douglas Hackney...ok to cover
Electrical Rough-In8/23/20188/24/20188/24/2018AFAIL
DetailsRock A. Hudson
Addition at rear of House, enter thru iron side gate.
Any questions..... call. Phone #: ###-#### Inspection requested via web by Douglas Hackney

680.27(C)- Heaters shall not be located with in 5' horizontal of inside edge of tub.
680.43(A)- All 120 volt 15 and 20 amp receptacle outlets shall be more than 6' from inside edge of hot tub.
680.43(B)- Lighting outlets located above or with in 5' horizontal of inside edge with GFCI protection shall not be with in 7'6" of waters edge. exception- recessed or surface mounted non-metallic or metallic with metallic isolated from contact permited below 7'6" if plastic or glass lense globe, GFCI protected, and damp location rated.
680.43(C)- Switches shall not be located with in 5' measured horizontal from inside edge of hot tub.
Discussed exhaust fan located below deck shall not need horizontal clearance due to barrier however bonding and GFCI protection required.
Issue PAID IN FULL permit  8/21/2018 DONE
Payment received via Govolutions
Application received  8/21/2018 DONE
This permit was created on the web by Douglas Hackney