First Notice | 11/20/2018 | 11/20/2018 | 2/10/2020 | | DONE |
Tom Saunders
|
|
|
|
Final | 11/19/2018 | 11/20/2018 | 11/20/2018 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley...corrections made...ok to final
|
Final | 11/12/2018 | 11/13/2018 | 11/13/2018 | A | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley... 1...GFI protection for all receptacles in garage area..120V and 240V 2..exterior outlet needs backing plate 3..ventilation system needs installed and working 4..air compressor needs installed for power verification
|
Permanent Service | 10/10/2018 | 10/10/2018 | 10/10/2018 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley Breakers rated at 65K and no AFC calc given, giving p/s ok being the breakers are rated so high....Contractor will having posting for final..
p/s u/g n ok
|
Electrical Rough-In | 9/26/2018 | 9/26/2018 | 9/26/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley Shop area and back office wall rough in ok cover
|
Electrical Rough-In | 9/20/2018 | 9/21/2018 | 9/21/2018 | A | PASS |
Rock A. Hudson
|
|
|
Request for cover Phone #: ###-#### Inspection requested via web by Tyler Ridley Check notes on ELE18-03086. Underground in slab Phone #: ###-#### Inspection requested via web by Kotton Corder Spoke with electrical contractor and owner as per NEC 511.3 to declassify minor repair garage and office areas minimum ventilation 4 or more air exchanges per hour with supply and outlet with in 12" of floor shall be provided by final so no electrical issues remain. Stamped Documentation must be provided. Under slab rough in for garage area rough in ok cover. New contractor taking over job. Office walls only rough in ok cover
|
Electrical Rough-In | 9/17/2018 | 9/17/2018 | 9/17/2018 | P | PASS |
Eric Story
|
|
|
Request to cover for street lighting Phone #: ###-#### Inspection requested via web by Tyler Ridley U/G on east and west of property ok to cover
|
Electrical Rough-In | 9/14/2018 | 9/14/2018 | 9/14/2018 | P | PASS |
Daryl DeGrange
|
|
|
Ground cover Phone #: ###-#### Inspection requested via web by Tyler Ridley Rough-in ok cover trench north side of structure to street sign
|
Electrical Rough-In | 8/22/2018 | 8/22/2018 | 8/22/2018 | P | PASS |
Tom Saunders
|
|
|
Cover Inspection Phone #: ###-#### Inspection requested via web by Tyler Ridley...ground work for parking lot lights...ok to cover
|
Issue PAID IN FULL permit | | | 8/22/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/22/2018 | | DONE |
|
|
|
This permit was created on the web by Tyler Ridley
|