Final | 10/14/2018 | 10/15/2018 | 10/15/2018 | A | PASS |
James Ady
|
|
|
Key is under rock by the man door of garage in back Phone #: ###-#### Inspection requested via web by Kevin Heideman corrections made final ok
|
Final | 10/10/2018 | 10/11/2018 | 10/11/2018 | A | FAIL |
James Ady
|
|
|
key is behind the shop under rock Phone #: ###-#### Inspection requested via web by Kevin Heideman 210.8 All kitchen receps shall be gfci protected( East wall) 110.3 Equipment shall be installed as per man. specs.( Kitchen gfci west wall open grnd. Replaced receps in house Rev polarity. Dead recep East wall living room.)
|
Permanent Service | 8/22/2018 | 8/23/2018 | 8/23/2018 | A | CANC |
Eric Story
|
|
|
The front door will be unlocked. If not the key is under a brick on the backside of the shop by man door Phone #: ###-#### Inspection requested via web by Kevin Heideman Needed rough-in for kitchen and bath
|
Electrical Rough-In | 8/23/2018 | 8/23/2018 | 8/23/2018 | P | PASS |
Eric Story
|
|
|
The front door will be unlocked. If not the key is under a brick on the backside of the shop by man door Phone #: ###-#### Inspection requested via web by Kevin Heideman Kitchen and hall bath ok to cover
|
Issue PAID IN FULL permit | | | 8/22/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/22/2018 | | DONE |
|
|
|
This permit was created on the web by Kevin Heideman
|