Final | 1/25/2019 | 1/25/2019 | 1/25/2019 | P | PASS |
Tom Saunders
|
|
|
Lock box is on the front door, code 1976. If you have any questions please feel free to contact CJ ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan.. corrections made...ok to final
|
Final | 1/24/2019 | 1/24/2019 | 1/24/2019 | P | FAIL |
Tom Saunders
|
|
|
There is a lock box on the front door, code 1976. If you have any questions please feel free to contact CJ ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan.... 1) luminaire (Fan) on patio shall be rated for damp location - verify 410.10 2) exposed wire at patio fan 422.19 box not rated for fan installation - 422.18 oulet box shall be completely covered - 422.20 Article 410, 410.20, 410.21, 410.10(A) 3) island outlet has no power 4) water heater needs disconnect or breaker lock out - 422.31 5) furnace disconnect shall have permanent marking of ON/OFF - toggle switch 422.34, 422.35
|
Rough-In Permanent Service | 10/23/2018 | 10/24/2018 | 10/24/2018 | A | PASS |
Eric Story
|
|
|
Lock box code 1976. If you have any questions please feel free to contact Jake ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Rough-in ok to cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 8/22/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/22/2018 | | DONE |
|
|
|
This permit was created on the web by Clayton Morgan
|