Final | 11/28/2018 | 11/28/2018 | 11/28/2018 | P | PASS |
Tom Saunders
|
|
|
Garage Code 4053 Phone #: ###-#### Inspection requested via web by Dean Gernaat... corrections made...ok to final
|
Final | 11/26/2018 | 11/27/2018 | 11/27/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Garage Code 4053 Phone #: ###-#### Inspection requested via web by Dean Gernaat 210.8- All 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. 1st nook receptacle to right of kitchen sink. 210.52(C)- Pantry counter work space shall have receptacle outlets located so that no point measured along wall line is more than 24" from a receptacle outlet. 348.30(A)- FMC shall be scured with in 12" of island receptacle box. 404.9(A), 406.6- All garage cover plates shall be installed. 408.4- circuit directory shall be complete. GFCI breaker will not reset. 410.16(A)- LED and incandecent luminaires located in master closet shall have totally enclosed lamps.
|
Rough-In Permanent Service | 9/6/2018 | 9/7/2018 | 9/7/2018 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Dean Gernaat p/s u/g n ok
|
Issue PAID IN FULL permit | | | 9/5/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/5/2018 | | DONE |
|
|
|
This permit was created on the web by Dean Gernaat
|