Final | 11/28/2018 | 11/29/2018 | 11/29/2018 | A | PASS |
Tom Saunders
|
|
|
Thank you. Phone #: ###-#### Inspection requested via web by CHRIS CARMINE... corrections made...ok to final final is for shell wiring only...interior wiring is ID Power training center
|
Final | 11/27/2018 | 11/28/2018 | 11/28/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Thank you. Phone #: ###-#### Inspection requested via web by CHRIS CARMINE 210.8(B)- All single phase receptacles and 3 phase receptacles 150 volts or less to ground located outdoors shall have GFCI protection. 422.31(B)- Permanently connected appliances rated 300 va or more shall have a disconnecting means located with in 50' and with in sight. 110.25 lock out acceptacle.
|
Electrical Rough-In | 10/30/2018 | 10/31/2018 | 10/31/2018 | P | PASS |
Tom Saunders
|
|
|
Thank you. Phone #: ###-#### Inspection requested via web by CHRIS CARMINE...ceiling ok to cover-training building
|
Electrical Rough-In | 9/6/2018 | 9/7/2018 | 9/7/2018 | A | PASS |
Tom Saunders
|
|
|
UFER PLEASE. THANKS Phone #: ###-#### Inspection requested via web by CHRIS CARMINE....concrete encased rebar..ok to cover
|
Issue PAID IN FULL permit | | | 9/5/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/5/2018 | | DONE |
|
|
|
This permit was created on the web by CHRIS CARMINE
|
First Notice | 11/29/2018 | 11/29/2018 | | | |
Tom Saunders
|
|
|
|