Final | 12/20/2018 | 12/21/2018 | 12/21/2018 | A | PASS |
James Ady
|
|
|
please call Nick for access to home 30-45 min ahead of time at ###-#### Phone #: ###-#### Inspection requested via web by A.M.E. Office corrections made final ok
|
Final | 11/7/2018 | 11/9/2018 | 11/9/2018 | A | FAIL |
James Ady
|
|
|
CALL JAMES WITH QUESTIONS ###-#### Phone #: ###-#### Inspection requested via web by A.M.E. Office Lights missing in hall down hall bath. 210.52C5. Countertop receps shall be within 20in above countertop to be considered work surface recep.. (Rt and Lt of cooktop.
|
Electrical Rough-In | 9/20/2018 | 9/21/2018 | 9/21/2018 | A | PASS |
James Ady
|
|
|
call James with questions ###-#### Phone #: ###-#### Inspection requested via web by A.M.E. Office whole house remodel Rough in ok
|
Electrical Rough-In | 9/19/2018 | 9/20/2018 | 9/20/2018 | A | FAIL |
James Ady
|
|
|
garage code is 4211 call james with questions ###-#### Phone #: ###-#### Inspection requested via web by A.M.E. Office 210.70A2(2) Dwelling units with grade level exterior doors shall have Exterior and interior lighting controll.(Down bed, Back door) 210.52A2. Recep shall be within 6ft of door. Right side of down bed door.
|
Issue PAID IN FULL permit | | | 9/17/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/17/2018 | | DONE |
|
|
|
This permit was created on the web by A.M.E. Office
|