Final | 11/19/2018 | 11/19/2018 | 11/19/2018 | P | PASS |
Tom Saunders
|
|
|
Ben Phone #: ###-####...corrections made...ok to final
|
Final | 11/13/2018 | 11/14/2018 | 11/14/2018 | P | FAIL |
Tom Saunders
|
|
|
Ben Phone #: ###-####.. 1..panel shall be legibly identified as to its clear and specific purpose or use..408.4 2..closet lights too close to closet shelf or rod..410.16 3..riser shall be strapped within 3ft of meter 4..sealtite shall be strapped within 8" of disconnect
|
Permanent Service | 10/15/2018 | 10/19/2018 | 10/19/2018 | P | PASS |
Eric Story
|
|
|
Ben Phone #: ###-#### p/s o/h rec ok
|
Electrical Rough-In | 10/2/2018 | 10/3/2018 | 10/3/2018 | A | PASS |
Eric Story
|
|
|
Ben Phone #: ###-#### Addition ok to cover, Also spoke about service change and allowing to re-energize once grounding and feeders are installed
|
Conference | 9/17/2018 | 9/18/2018 | 9/18/2018 | P | DONE |
Eric Story
|
|
|
Ben-please call an hour prior to meet to meet Phone #: ###-#### Discussed service hange due to split bus type panel board and service entrance to sup panel
|
Application received | | | 9/17/2018 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/17/2018 | | DONE |
|
|
|
|