Final | 10/30/2018 | 10/30/2018 | 10/30/2018 | P | PASS |
Tom Saunders
|
|
|
Repairs are complete. Phone #: ###-#### Inspection requested via web by Kendra Lanham... corrections complete...ok to final
|
Final | 10/22/2018 | 10/22/2018 | 10/22/2018 | P | FAIL |
Tom Saunders
|
|
|
Final for office area and service Phone #: ###-#### Inspection requested via web by Kendra Lanham... 1..panel shalle be completely labelled-408.4 2..breaker feeding subpanel? exceeds manufacturers rating-100A max-110.3(B)
|
Permanent Service | 10/1/2018 | 10/2/2018 | 10/2/2018 | A | PASS |
Rock A. Hudson
|
|
|
Inspector requested mast to be elevated for clearance over parking area. Need a pass for coordination with Idaho Power Phone #: ###-#### Inspection requested via web by Kendra Lanham p/s o/h rec ok
|
Rough-In Permanent Service | 9/24/2018 | 9/25/2018 | 9/25/2018 | A | FAIL |
Daryl DeGrange
|
|
|
Please inspect 200amp overhead service and rough-in inspection on office addition. Call Todd ###-#### if you have any questions Phone #: ###-#### Inspection requested via web by Kendra Lanham 230.24(B) (2) Service entance conductors require clearance of 12ft. of lowest point over residential driveway
|
Electrical Rough-In | 9/25/2018 | 9/25/2018 | 9/25/2018 | P | PASS |
Daryl DeGrange
|
|
|
Please inspect 200amp overhead service and rough-in inspection on office addition. Call Todd ###-#### if you have any questions Phone #: ###-#### Inspection requested via web by Kendra Lanham Rough-in ok cover office area
|
Issue PAID IN FULL permit | | | 9/24/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/24/2018 | | DONE |
|
|
|
This permit was created on the web by Kendra Lanham
|