Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE18-03757
StatusFinaled
Name DIEHL EMILY
Site Address 2428 N CHITWOOD WAY
Project NameMace shop
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Addition: Electrical to RV garage
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/27/201812/28/201812/28/2018APASS
DetailsTom Saunders
Justin Phone #: ###-####...
corrections made...ok to final
Final12/26/201812/26/201812/26/2018PFAIL
DetailsTom Saunders
Justin Phone #: ###-####...

1..all 120 volt outlets in shop shall have GFCI protection
2..outside outlet HD/inuse cover needs installed properly
Electrical Rough-In11/5/201811/6/201811/6/2018APASS
DetailsTom Saunders
Justin Phone #: ###-####...
rough in ok to cover
Electrical Rough-In10/31/201811/1/201810/31/2018APASS
DetailsDaryl DeGrange
Justin Phone #: ###-#### Replacement of defective service panel interior, r/i ok
Electrical Rough-In10/3/201810/3/201810/3/2018PCANC
DetailsRock A. Hudson
Justin Phone #: ###-####
Needed permanent service inspection.
Permanent Service10/3/201810/3/201810/3/2018PPASS
DetailsRock A. Hudson
Justin Phone #: ###-####
p/s o/h n ok
Electrical Rough-In10/2/201810/3/201810/3/2018AFAIL
DetailsRock A. Hudson
Justin-husband Phone #: ###-####
250.92(A)- All non current carrying metal parts shall be bonded. Metal nipple installed in concentric holes not bonded.
Conference10/2/201810/2/201810/2/2018PPASS
DetailsRock A. Hudson
Justin Phone #: ###-####
Discussed 200amp service and overhead clearence of service entrance conductors. Miscommumication with Idaho power on how easy it would be to get around tall shop and refeed house. Roof pitch on shop 3x12 suggested building a stand off on corner of shop and stay below roof to avoid above roof requirements. Has provided a grounding electrode system of ground rods 5'5" apart. Concrete encased electrode is provided on east wall that will be connected when framing complete on that wall. Discussed interior receptacle locations and types and required lights for interior and man doors.
Issue PAID IN FULL permit  10/1/2018 DONE
Payment received via Govolutions
Application received  10/1/2018 DONE
This permit was created on the web by Justin Mace