Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberELE18-03769
StatusFinaled
Name B & B ELECTRIC
Site Address 6172 N PIERCE PARK LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: New home electrical work
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/14/20192/14/20192/14/2019PPASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Eric Brown Corrections made. Ok final.
Final2/12/20192/12/20192/12/2019PFAIL
DetailsMark Moncarr
Thank you Phone #: ###-#### Inspection requested via web by Eric Brown All electrical work associated with home is good. A/C disconnects for mini split system needs corrections made by heating company. In disc to right, neutral wires need identified as hot conductors. NM cable in left disc cannot be used in outdoor damp or wet locations. Bushing also need for wires exiting wall into disc. Western Heating and Air were the installers.
Rough-In Permanent Service10/5/201810/5/201810/5/2018PPASS
DetailsMark Moncarr
Thank you and have a great day. Phone #: ###-#### Inspection requested via web by Eric Brown p/s u/g n ok
Issue PAID IN FULL permit  10/2/2018 DONE
Payment received via Govolutions
Application received  10/2/2018 DONE
This permit was created on the web by Bonnie Page