Final | 12/19/2018 | 12/20/2018 | 12/20/2018 | A | PASS |
Mark Moncarr
|
|
|
Call Jose Guerrero with any concerns. Phone #: ###-#### Inspection requested via web by Jose Guerrero Ok final.
|
Electrical Rough-In | 10/15/2018 | 10/16/2018 | 10/16/2018 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Jose Guerrero Corrections fixed Rough-in ok to cover p/s u/g n ok
|
Electrical Rough-In | 10/15/2018 | 10/15/2018 | 10/15/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Jose Guerrero 210.52- No point measured a long floor line shall be more than 6' from a receptacle outlet. In nook first receptacle outlet more than 8' from end of cabinet. receptacles serving counter top areas do not count for general layout. 334.30- NM cable shall have supports not to exceed 4 1/2'. 14-2 to can over stairs hangs below truss with supports over 4 1/2'. 800.100(B)(2)- Single family dwelling units with grounded electrical systems shall have gounding conductors connected to grounding electrode system.
|
Issue PAID IN FULL permit | | | 10/15/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/15/2018 | | DONE |
|
|
|
This permit was created on the web by Jose Guerrero
|