VOIDED CHANGE STATUS | | | 11/26/2018 | | DONE |
|
|
|
This permit was pulled by sq. ft. Left message 10/16/18 informing Amped Electric to call me back to correct the permit. They pulled a new permit (see ELE18-04502) correctly by the fixtures. Voided this permit out (both permit have passed rough ins)
|
Rough-In Permanent Service | 10/16/2018 | 10/16/2018 | 10/16/2018 | P | CANC |
Rock A. Hudson
|
|
|
Call first please Inspect trench for feeder Phone #: ###-#### Inspection requested via web by Eddy Udry Needed underground rough in only.
|
Electrical Rough-In | 10/16/2018 | 10/16/2018 | 10/16/2018 | P | PASS |
Rock A. Hudson
|
|
|
Call first please Inspect trench for feeder Phone #: ###-#### Inspection requested via web by Eddy Udry Discussed 250.32(B) equipment ground and grounding electrodes required at seperate house structure. Back window has all operable panes with no wall space to serve kitchen counter space, area to be treated as an island. Full length cabinets planned to most walls in living space shall provide floor or toe kick receptacles to serve wall space. Underground from garage to house rough in ok cover
|
Issue PAID IN FULL permit | | | 10/16/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/16/2018 | | DONE |
|
|
|
This permit was created on the web by Eddy Udry
|
Telephone call | | | 10/16/2018 | | DONE |
|
|
|
Left voicemail for Eddy to inform him the permit needs to be pulled by the fixture and not sq ft.
|