First Notice | 11/21/2018 | 11/21/2018 | 2/21/2019 | | DONE |
Eric Story
|
|
|
This permit finaled on the web by Winters LLC
|
Final | 11/20/2018 | 11/21/2018 | 11/21/2018 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Winters LLC Occ card signed Final ok
|
Final | 11/1/2018 | 11/1/2018 | 11/1/2018 | P | NR |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Winters LLC wrong permit called in
|
Electrical Rough-In | 10/25/2018 | 10/25/2018 | 10/25/2018 | P | PASS |
Eric Story
|
|
|
Re-inspection please Phone #: ###-#### Inspection requested via web by Winters LLC
Correction fixed ceiling only ok to cover
|
Electrical Rough-In | 10/23/2018 | 10/24/2018 | 10/24/2018 | A | FAIL |
Tom Saunders
|
|
|
Ceiling inspection please Phone #: ###-#### Inspection requested via web by Winters LLC... 1..luminaires shall be securely fastened to the ceiling framing...earthquake clips-410.36(B) 2..low volt wiring shall be removed or supported off ceiling grid
|
Electrical Rough-In | 10/18/2018 | 10/19/2018 | 10/19/2018 | A | PASS |
Eric Story
|
|
|
Wall inspection please Phone #: ###-#### Inspection requested via web by Winters LLC Walls only ok to cover(could not locate print on site) Go through door 10352 for better access
|
Issue PAID IN FULL permit | | | 10/18/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 10/18/2018 | | |
|
|
|
|
Application received | | | 10/18/2018 | | DONE |
|
|
|
This permit was created on the web by Winters LLC
|