Final | 1/2/2019 | 1/3/2019 | 1/3/2019 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Ok final.
|
Rough-In Permanent Service | 10/18/2018 | 10/19/2018 | 10/19/2018 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson 125a brkr needs replaced with 100a max at 200a meter main. 100a brkr is max used in lowest position of bussing as per manu instructions. Will need to see upon final. p/s o/h n ok
|
Issue PAID IN FULL permit | | | 10/18/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/18/2018 | | DONE |
|
|
|
This permit was created on the web by Ryan Wilson
|