Final | 1/28/2019 | 1/29/2019 | 1/29/2019 | A | PASS |
James Ady
|
|
|
Call for access code, thank you Phone #: ###-#### Inspection requested via web by kim grundhauser Corrections made final ok
|
Final | 1/27/2019 | 1/28/2019 | 1/28/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Call for access code thank you Phone #: ###-#### Inspection requested via web by kim grundhauser 210.8- GFCI devices shall be located in readily accessible locations. Soffit receptacle west garage. 410.10(D)- Luminaires located in shower stall shall be rated for wet locations. Master shower confirm rating of trim and lamp.
|
Rough-In Permanent Service | 11/1/2018 | 11/1/2018 | 11/1/2018 | P | PASS |
James Ady
|
|
|
Call with any questions. Thank you. Phone #: ###-#### Inspection requested via web by kim grundhauser rough in ok p/s u/g n ok
|
Issue PAID IN FULL permit | | | 10/30/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/30/2018 | | DONE |
|
|
|
This permit was created on the web by kim grundhauser
|