Final | 5/9/2019 | 5/10/2019 | 5/10/2019 | A | PASS |
Rock A. Hudson
|
|
|
Final for Units 121, 123, 223 ; 323. Any questions call Mike Brown @ ###-####. Inspection requested via web by Bonnie Page Added 119. West building complete. Final ok
|
Final | 4/25/2019 | 4/25/2019 | 4/25/2019 | P | PART |
Rock A. Hudson
|
|
|
For Units: 109, 111, 113, 115 ; 117 Please call Mike Brown w/any questions ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Bonnie Page Previous item noted corrected. Units noted TCO ok.
|
Final | 4/23/2019 | 4/24/2019 | 4/24/2019 | A | PART |
Rock A. Hudson
|
|
|
Please final units 101, 103, 105, 107, 201 ; 203. Any questions, please call Mike Brown ###-#### Phone #: ###-#### Inspection requested via web by Bonnie Page Ranges and dryer cords require installation to be done by electrical contractor. 250.140- Bonding strap shall be removed for 4 wire installation. Will check in future. 225.31 &32- A disconnecting means shall be provided for all ungrounded conductors that supply structure and shall be located on such structure. Units noted TCO ok
|
Rough-In Permanent Service | 11/29/2018 | 11/30/2018 | 11/30/2018 | A | PASS |
Rock A. Hudson
|
|
|
West Building, Units 121, 123, 223, 323 Phone #: ###-#### Inspection requested via web by Bonnie Page Units noted rough in ok cover. 22k highest available fault current. p/s u/g n ok
|
Electrical Rough-In | 11/16/2018 | 11/16/2018 | 11/16/2018 | P | PASS |
Rock A. Hudson
|
|
|
Please perform a R/I inspection on Units: 119, 117, 115, 113, 111. Any questions please contact Mike ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Bonnie Page phone demark and catv boxes above and below Asked about phone demark and catv boxes above and below electrical service. 110.26- Dedicated electrical space for electrical equipment. Informed these items are electrical equipment so ok to be in this space. Before permanent service temp power for heat in each unit a 50 amp 240 volt receptacle installed at range receptacle location shall have GFCI protection as per 590.6(B). Rooms noted rough in ok cover.
|
Rough-In Permanent Service | 11/3/2018 | 11/5/2018 | 11/5/2018 | P | FAIL |
Rock A. Hudson
|
|
|
ROUGH IN COVER ON FIRST 6 UNITS OF WEST BUILDING. AND PERMANENT SERVICE FOR METER PACKS ON WEST BUILDING Phone #: ###-#### Inspection requested via web by mike brown 110.24- Available fault current shall be posted prior to permenant service inspection.
|
Electrical Rough-In | 11/5/2018 | 11/5/2018 | 11/5/2018 | P | PASS |
Rock A. Hudson
|
|
|
ROUGH IN COVER ON FIRST 6 UNITS OF WEST BUILDING. AND PERMANENT SERVICE FOR METER PACKS ON WEST BUILDING Phone #: ###-#### Inspection requested via web by mike brown Units 101, 105, 107, 109, 201, 203 rough in ok cover
|
Issue PAID IN FULL permit | | | 11/2/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/2/2018 | | DONE |
|
|
|
This permit was created on the web by Bonnie Page
|
First Notice | 5/10/2019 | 5/10/2019 | | | |
Rock A. Hudson
|
|
|
|