Final | 8/16/2019 | 8/16/2019 | 8/16/2019 | P | PASS |
James Ady
|
|
|
Call Brodie with any questions. Phone #: ###-#### Inspection requested via web by William Salts Corrections made final ok
|
Final | 8/9/2019 | 8/12/2019 | 8/12/2019 | P | FAIL |
James Ady
|
|
|
Please call Brodie with any questions Phone #: ###-#### Inspection requested via web by William Salts 210.8 garage receps shall be gfci protected 433 a/c overcurrent shall not exceed max rating on nameplate. 408 Panel schedule shall be acuratly and clearly labeled 422. cord and plug used as disc shal be accessible 110.3. front wheatherproof missing internal trim and also protecting rear w/p
|
Final | 8/7/2019 | 8/8/2019 | 8/8/2019 | P | NR |
James Ady
|
|
|
Please call Juan with any questions Phone #: ###-#### Inspection requested via web by William Salts Missing item throughout. Not ready re-call
|
Fees Due Hold | 2/14/2019 | | 8/7/2019 | | DONE |
|
|
|
|
Conference | 2/13/2019 | 2/14/2019 | 2/14/2019 | A | CANC |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by William Salts needed rough in
|
Electrical Rough-In | 2/14/2019 | 2/14/2019 | 2/14/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by William Salts Kitchen layout will not change. Exhisting receps locations ok. Corrections made rough in ok
|
Electrical Rough-In | 2/12/2019 | 2/13/2019 | 2/13/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Call Wayne with any questions, ###-####. Phone #: ###-#### Inspection requested via web by William Salts Corrections not complete, receptacle added in master bed between bath and closet only. Complete rest of corrections and recall
|
Reinspection Fee (no hold) | 2/13/2019 | 2/13/2019 | 2/13/2019 | P | PASS |
Rock A. Hudson
|
|
|
Call Wayne with any questions, ###-####. Phone #: ###-#### Inspection requested via web by William Salts corrections not complete
|
Electrical Rough-In | 2/8/2019 | 2/11/2019 | 2/11/2019 | A | FAIL |
James Ady
|
|
|
Call Wayne with any questions, ###-####. Phone #: ###-#### Inspection requested via web by William Salts 210.52. Recep needed on Garage seperation wall Living room side., Front office, Back side of closet. Master bed between Closet door and Bathroom door. 210.52D within 3ft of 2nd master bath vanity. Remove all wiring from swith in tub footprint.
|
Electrical Rough-In | 1/30/2019 | 1/30/2019 | 1/30/2019 | P | PASS |
James Ady
|
|
|
Rough in for garage and utility room addition. Please call Wayne at the number listed or Kaden at ###-#### when on the way. Phone #: ###-#### Inspection requested via web by William Salts Garage and utility room only ok to cover
|
Rough-In Permanent Service | 11/19/2018 | 11/20/2018 | 11/20/2018 | A | NR |
James Ady
|
|
|
Please call Kaden when on the way at ###-####. Phone #: ###-#### Inspection requested via web by William Salts
|
Permanent Service | 11/20/2018 | 11/20/2018 | 11/20/2018 | P | PASS |
James Ady
|
|
|
Please call Kaden when on the way at ###-####. Phone #: ###-#### Inspection requested via web by William Salts p/s u/g n ok
|
Issue PAID IN FULL permit | | | 11/5/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/5/2018 | | DONE |
|
|
|
This permit was created on the web by William Salts
|